Fire retardant cable(Fireguard)
300/500V PVC Insulated, PVC Sheathed Power Cables to BS 6004 (Single Core)
FGD300 05VV-U/R (CU/PVC/PVC 300/500V Class 1/2)
BS Code: 6181Y (CU/PVC/PVC)
APPLICATION:
The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. This product type is TUV approved.
STANDARDS:
Basic design to BS 6004: 2012
FIRE PERFORMANCE:
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2 |
---|
VOLTAGE RATING:
300/500V
CABLE CONSTRUCTION:
Conductor:Annealed copper conductor, class 1 (1.0mm² to 2.5mm²) or class 2 (4mm² to 35mm²) according to BS EN 60228.
Insulation:PVC Type TI 1 according to BS EN 50363-3.
Outer Sheath:PVC Type 6 according to BS 7655-4.2.
Outer Sheath Option:UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
COLOUR CODE:
Insulation Colour | Brown or blue. |
---|---|
Sheath Colour | Grey, other colours can be offered upon request. |
Physical AND THERMAL PROPERTIES:
Maximum temperature range during operation (PVC) | 70°C |
---|---|
Maximum short circuit temperature (5 Seconds) | 160°C |
Minimum bending radius | Up to 10mm² - Fixed: 3 x overall diameter |
10mm² to 25mm² - Fixed: 4 x overall diameter |
CONSTRUCTION PARAMETERS:
Conductor | FGD300 05VV-U/R | ||||
---|---|---|---|---|---|
No. of Cores x Cross Section | Class of Conductor | Nominal Insulation Thickness | Nominal Sheath Thickness | Maximum Overall Diameter | Approx. Weight |
No.xmm² | mm | mm | kg/km | ||
1x1.0 |
1 |
0.6 |
0.8 |
4.5 |
27 |
1x1.5 |
1 |
0.7 |
0.8 |
5.0 |
36 |
1x2.5 |
1 |
0.8 |
0.8 |
5.7 |
52 |
1x4.0 |
2 |
0.8 |
0.9 |
6.7 |
76 |
1x6.0 |
2 |
0.8 |
0.9 |
7.3 |
100 |
1x10 |
2 |
1.0 |
0.9 |
8.8 |
160 |
1x16 |
2 |
1.0 |
1.0 |
10.1 |
230 |
1x25 |
2 |
1.2 |
1.1 |
12.1 |
340 |
1x35 |
2 |
1.2 |
1.1 |
13.5 |
440 |
ELECTRICAL PROPERTIES:
Conductor Operating Temperature | 70°C |
---|---|
Ambient Temperature | 30° |
Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D1A
Conductor cross- sectional area |
Reference Method A (enclosed in conduit in thermally insulating wall etc) | Reference Method B (enclosed in conduit on a wall or in trunking etc) | Reference Method C (clipped direct) | Reference Method F (in free air or on a perforated cable tray horizontal or vertical etc) | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Touching | Spaced by one cable diameter | ||||||||||
2 cables, single-phase a.c. or d.c. | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c. flat and touching | 3 or 4 cables, three-phase a.c. flat and touching or trefoil | 2 cables, single-phase a.c. or d.c. flat | 3 cables, three-phase a.c. flat | 3 cables, three-phase a.c. trefoil | 2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat | ||
Horizontal | Vertical | ||||||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
mm² |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
1.0 |
11.0 |
10.5 |
13.5 |
12.0 |
15.5 |
14 |
- |
- |
- |
- |
- |
1.5 |
14.5 |
13.5 |
17.5 |
15.5 |
20 |
18 |
- |
- |
- |
- |
- |
2.5 |
20 |
18 |
24 |
21 |
27 |
25 |
- |
- |
- |
- |
- |
4.0 |
26 |
24 |
32 |
28 |
37 |
33 |
- |
- |
- |
- |
- |
6.0 |
34 |
31 |
41 |
36 |
47 |
43 |
- |
- |
- |
- |
- |
10 |
46 |
42 |
57 |
50 |
65 |
59 |
- |
- |
- |
- |
- |
16 |
61 |
56 |
76 |
68 |
87 |
79 |
- |
- |
- |
- |
- |
25 |
80 |
73 |
101 |
89 |
114 |
104 |
131 |
114 |
110 |
146 |
130 |
35 |
99 |
89 |
125 |
110 |
141 |
129 |
162 |
143 |
137 |
181 |
162 |
Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D1B
Nominal Cross Section Area |
2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Ref. Methods A and B (enclosed in conduit or trunking) | Ref. Methods C & F(clipped direct, on trays or in free air) | Ref. Methods A & B (enclosed in conduit or trunking | Ref. Methods C & F (clipped direct, on trays or in free air) | |||||||||||||||||||
Cables touching | Cables spaced* | Cables touching, Trefoil | Cables touching, Flat | Cables spaced*, Flat | ||||||||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | ||||||||||||||
mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | ||||||||||||||
1.0 |
44 |
44 |
44 |
44 |
38 |
38 |
38 |
38 |
||||||||||||||
1.5 |
29 |
29 |
29 |
29 |
25 |
25 |
25 |
25 |
||||||||||||||
2.5 |
18 |
18 |
18 |
18 |
15 |
15 |
15 |
15 |
||||||||||||||
4.0 |
11 |
11 |
11 |
11 |
9.5 |
9.5 |
9,5 |
9.5 |
||||||||||||||
6.0 |
7.3 |
7.3 |
7.3 |
7.3 |
6.4 |
6.4 |
6.4 |
6.4 |
||||||||||||||
10 |
4.4 |
4.4 |
4.4 |
4.4 |
3.8 |
3.8 |
3.8 |
3.8 |
||||||||||||||
16 |
2.8 |
2.8 |
2.8 |
2.8 |
2.4 |
2.4 |
2.4 |
2.4 |
||||||||||||||
|
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
25 |
1.75 |
1.8 |
0.33 |
1.8 |
1.75 |
0.20 |
1.75 |
1.75 |
0.29 |
1.8 |
1.5 |
0.29 |
1.55 |
1.5 |
0.175 |
1.5 |
1.5 |
0.25 |
1.55 |
1.5 |
0.32 |
1.55 |
35 |
1.25 |
1.3 |
0.31 |
1.3 |
1.25 |
0.195 |
1.25 |
1.25 |
0.28 |
1.3 |
1.1 |
0.27 |
1.10 |
1.1 |
0.170 |
1.1 |
1.1 |
0.24 |
1.10 |
1.1 |
0.32 |
1.15 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance